<ArticleTitle>Recognition and Location of Power Transformer Turn to Turn Fault by Analysis of Winding Imposed Forces</ArticleTitle>
<VernacularTitle>شناسایی و مکان یابی خطای اتصال حلقه در ترانسفورماتور قدرت با استفاده از تحلیل نیروهای تحمیل شده ی سیم پیچ</VernacularTitle>
			<FirstPage>227</FirstPage>
			<LastPage>234</LastPage>
			<ELocationID EIdType="pii">783</ELocationID>
			
<ELocationID EIdType="doi">10.22098/joape.2019.5735.1428</ELocationID>
			
			<Language>EN</Language>
<AuthorList>
<Author>
					<FirstName>A.</FirstName>
					<LastName>Torkaman</LastName>
<Affiliation>Department of Electrical Engineering, Malayer University, Malayer, Iran.</Affiliation>

</Author>
<Author>
					<FirstName>V.</FirstName>
					<LastName>Naeini</LastName>
<Affiliation>Department of Electrical Engineering, Malayer University, Malayer, Iran.</Affiliation>

</Author>
</AuthorList>
				<PublicationType>Journal Article</PublicationType>
			<History>
				<PubDate PubStatus="received">
					<Year>2019</Year>
					<Month>01</Month>
					<Day>16</Day>
				</PubDate>
			</History>
		<Abstract>Turn to turn fault is one of the major internal failures in the power transformers that if it is not quickly detected, can be extended and led to a complete transformer breakdown. So, the diagnosis and location of the turn to turn fault of the power transformer, as one of the most important equipment in the power system, is the main objective of this paper. For this purpose, a detailed model of a three-phase transformer is presented by the finite element method (FEM) to investigate this fault in the different situations. Accordingly, the number of short-circuit turns as well as fault location, cause to generate the high forces between the short-circuit turns and the other healthy winding turns. Consequently, in this paper an appropriate method based on force analysis of winding turns for detecting, locating and determining fault severity is introduced.</Abstract>
		<ObjectList>
			<Object Type="keyword">
			<Param Name="value">turn to turn fault</Param>
			</Object>
			<Object Type="keyword">
			<Param Name="value">Recognition</Param>
			</Object>
			<Object Type="keyword">
			<Param Name="value">location</Param>
			</Object>
			<Object Type="keyword">
			<Param Name="value">imposed forces</Param>
			</Object>
			<Object Type="keyword">
			<Param Name="value">FEM</Param>
			</Object>
		</ObjectList>
<ArchiveCopySource DocType="pdf">https://joape.uma.ac.ir/article_783_aefb3bc0e1e1ae83c9f7d32fd012182a.pdf</ArchiveCopySource>